8 Alarms

TcForge alarms detect assembly-machine conditions such as missing parts, clamp feedback, force limits and abnormal position rates. They expose debounce, acknowledgment, severity and evaluation validity independently of device faults.

Navigation: ← Sequencing · Documentation home · HMI Integration →

8.1 Alarms vs. Faults

Concept Owner Recovery
Device fault FB_DeviceBase and the device's fault definitions Explicit device Reset() after correcting the cause.
Alarm A standalone alarm instance or an alarm composed by a device Valid clear evidence, configured off-delay, and acknowledgment when required.

Alarms do not extend FB_DeviceBase, own physical IO or automatically write the device fault history. An application may explicitly promote a selected alarm to a device fault. An alarm can also display a device's existing sts.header.faulted condition.

8.2 Severity Model

E_AlarmSeverity contains NONE, INFO, WARNING, CRITICAL and SHUTDOWN in increasing numeric order. NONE remains a valid configured value. Unknown enum values produce InvalidConfig.

An inactive alarm reports NONE. A valid active evaluation publishes cfg.common.eSeverity; invalid evaluation preserves the last established severity. FB_AlarmLimit reports the highest severity among its four child statuses. Severity is a display/classification value; it does not itself issue a machine stop.

8.3 Common Status: ST_Alarm_Sts

Field Meaning
enabled Echo of cfg.common.bEnable.
valid TRUE only when the alarm has a usable evaluation.
evaluationState Disabled, Valid, InvalidInput, InvalidConfig or Initializing.
raw Current condition before debounce when valid. FALSE during invalidity is not evidence that the condition cleared.
debounced Established condition after trip/clear delays; held during invalid evaluation.
active TRUE while the debounced condition or an outstanding latch remains.
latched An outstanding latch awaits acknowledgment, even if bRequireAck was subsequently disabled.
acked The outstanding latch has been acknowledged; this does not prove the condition cleared.
eSeverity Active severity, held during invalidity; NONE when inactive.
sMessage Echo of cfg.common.sMessage.
ackRequester Requester of the most recent acknowledgment of a latch.
tsTripped, tsCleared Last rising/falling edge timestamps of the established debounced condition.
tsAcked Last accepted acknowledgment timestamp when a latch existed.

The alarm owns its status. Consumers should display both active and valid: an inactive alarm with invalid evidence does not establish that the machine condition is normal.

Validity and recovery

Every concrete alarm has inpValid : BOOL := TRUE. Bind it to application signal quality when a value can be stale, disconnected or unavailable. Numeric alarms also classify IEEE NaN and infinity through integer-bit helpers before floating-point comparisons, arithmetic or conversions.

Invalid input/configuration and rate-history initialization reset pending transition timing. They preserve established debounced/active state, latch, severity and trip/clear timestamps. Ack may be recorded while invalid, but cannot release a latch without later valid clear evidence. Recovery starts the full off-delay from fresh valid clear samples; time without trustworthy evidence does not count toward clearing.

cfg.common.bEnable := FALSE is an explicit suppression operation that clears active/latch/ack state and reports Disabled. Use inpValid for communication loss. Changing bRequireAck affects future trips and cannot erase an existing unacknowledged latch.

8.4 Common Config: ST_Alarm_Cfg

Each concrete configuration contains common : ST_Alarm_Cfg. For example, use alarm.cfg.common.bEnable, not a flattened enable field. FB_AlarmLimit has a separate nested common configuration per level, such as alarm.cfg.Hi.common.bEnable.

Field Default Meaning
bEnable FALSE Explicitly enable evaluation; FALSE clears and suppresses the alarm.
tOnDelay T#0MS Continuous valid trip evidence required before activation.
tOffDelay T#0MS Continuous valid clear evidence required before releasing the condition.
bRequireAck FALSE New trips create an acknowledgment latch when TRUE.
eSeverity NONE Severity classification for valid active evaluation.
sMessage Empty Operator message, for example Clamp force above limit.

TIME is unsigned in TwinCAT. Zero disables the corresponding delay. The application writes configuration in the owning cyclic task; configuration and status are published read-only to OPC UA. Do not use external field writes as a configuration update mechanism.

8.5 Lifecycle

  1. Valid trip evidence must remain true for tOnDelay before the debounced condition becomes true.
  2. An active condition remains established until valid clear evidence lasts for tOffDelay.
  3. With acknowledgment required, the alarm also remains active until Ack. Ack while the condition holds records acknowledgment without clearing the alarm.
  4. Invalid evidence interrupts timing and preserves established state. Recovery must supply fresh evidence.

Changing trip/clear delays or acknowledgment policy restarts pending transition timing. Threshold direction/value and deviation mode/bound changes also restart timing, so new criteria cannot inherit timer credit from old criteria.

Latch and acknowledgment flags are VAR PERSISTENT. Persistence requires the application's TwinCAT persistent-data configuration and remains subject to the repository's restart/persistence qualification. Severity and timestamps are not a durable alarm-history store.

When those flags are restored, an unacknowledged latch still requires Ack. An acknowledged latch preserves that acknowledgment and requires valid clear evidence, without a second Ack merely because the runtime restarted. On the first enabled evaluation, a restored latch publishes the configured severity when that severity is recognized, even if process input is invalid. Subsequent invalid evaluations preserve the established severity. Configure the alarm before its first cyclic call; an explicitly disabled call clears the restored latch under the normal suppression policy.

8.6 FB_AlarmBase — The Shared Engine

FB_AlarmSimple, FB_AlarmThreshold, FB_AlarmDeviation and FB_AlarmRateOfChange extend the abstract base. FB_AlarmLimit instead composes four threshold instances and implements I_Alarm.

The base owns separate TON timers for trip and clear transitions, latch/ack state, timestamps, status, source locking and the operator mailbox. A child classifies its configuration and inputs, computes its raw condition only when valid, then calls _Evaluate once from its cyclic body:

_Evaluate(
    cfgCommon := cfg.common,
    bRawCondition := rawCondition,
    evaluation := evaluationState,
    resetTiming := criteriaChanged
);

The child supplies its own local condition, evaluation-state and configuration-change variables. _Evaluate is the protected implementation API; there is no _EvaluateCondition override or cycle guard. Each alarm instance must have one owning task and one cyclic evaluation per scan. Call only the limit ladder's body when using FB_AlarmLimit; its child calls are internal.

8.7 Concrete Alarms

8.7.1 FB_AlarmSimple

Inputs are cfg : ST_AlarmSimple_Cfg, inpActive : BOOL and inpValid. The output is sts : ST_Alarm_Sts. Use it for a missing-part condition or a device fault indication whose quality is known separately.

8.7.2 FB_AlarmThreshold

Inputs are cfg : ST_AlarmThreshold_Cfg, inpValue : REAL and inpValid. Configuration adds fThreshold, bFailHigh and bFailLow.

Exactly one direction must be selected while enabled. Both directions or neither direction produce InvalidConfig. Comparisons are strict: equality to the threshold does not trip. Non-finite thresholds are invalid configuration; non-finite input values are invalid input.

8.7.3 FB_AlarmLimit

Inputs are cfg : ST_AlarmLimit_Cfg, inpPv : REAL and inpValid. The ladder has HiHi, Hi, Lo and LoLo threshold configurations and child statuses.

HiHi suppresses Hi on rollup active flags, and LoLo suppresses Lo. Individual child statuses remain available. anyActive and eSeverity aggregate alarm state. The input-valid gate reaches every child; composite validity covers enabled levels only. Disabled unused levels do not invalidate an enabled level, while an entirely disabled ladder reports Disabled.

8.7.4 FB_AlarmDeviation

Inputs are cfg : ST_AlarmDeviation_Cfg, inpPv : REAL, inpSetpoint : REAL and inpValid.

  • Absolute mode: alarm outside fLowLimit..fHighLimit; the limits must be ordered. The unused setpoint does not affect validity.
  • Setpoint mode (bUseSetpoint := TRUE): alarm above setpoint plus fHighLimit, or below setpoint minus fLowLimit. Both deviations must be nonnegative.

All participating values must be finite. Bounds use LREAL intermediates so adding or subtracting large finite REAL values does not overflow.

8.7.5 FB_AlarmRateOfChange

Inputs are cfg : ST_AlarmRateOfChange_Cfg, inpPv : REAL and inpValid. outRateOfChange : LREAL reports units per second. Configuration adds finite, nonnegative fRateLimit; the alarm tests the absolute rate against it.

Rate uses the configured task period through F_GetTaskCycleTime() and LREAL arithmetic. The helper has millisecond resolution: use tasks of at least 1 ms. Zero period is invalid configuration. This is a per-task-sample rate, not a measurement of ADS arrival intervals or actual scheduling jitter.

Startup, re-enable, invalid input/configuration, rate-limit or debounce/ack-policy changes, a different task, and task-period changes discard history. The first valid sample reports Initializing and zero diagnostic rate; it cannot clear an existing alarm. The second valid sample supplies a usable rate.

Before assigning a different signal source, call application-only ReassignInput() in the owning task. It immediately invalidates rate history while preserving the established alarm. The next valid sample establishes the new baseline. A cycle with inpValid := FALSE also invalidates history.

8.8 Ack Semantics and I_Alarm

I_Alarm exposes the program methods Ack(eRequester) and LockSource(bLock). Direct program calls execute in the owning task. Ack validates requester identity and source locking; a locked alarm rejects operator acknowledgment with REJECTED_SOURCE_NOT_ALLOWED.

Repeated accepted acknowledgment of an existing latch refreshes tsAcked and ackRequester. Ack with no latch is an accepted no-op. FB_AlarmLimit.Ack cascades to its four levels.

External ADS/OPC UA clients use the queued RPC methods:

  1. Call OperatorAck(requestId) with a nonzero request ID unique across clients and PLC restarts.
  2. QUEUED means admitted to the mailbox, not acknowledged yet.
  3. Read OperatorCommandResult(requestId) for the owning task's execution result.

The RPC wrapper fixes the requester to OPERATOR. Ack and LockSource are not RPC-enabled. Admission may return busy or another rejection; follow the bounded mailbox protocol in HMI integration. A successful execution result still does not imply the alarm condition cleared.

8.9 Wiring Alarms to Devices

8.9.1 Device composes alarms internally

A device can own an alarm for a specific concern, such as clamp-force deviation. Its cyclic body supplies the signal and quality, evaluates the alarm once, then explicitly decides whether sts.active or invalid evaluation should affect the device. There is no automatic alarm-to-fault conversion.

8.9.2 Standalone alarm in a program

This complete program example supplies a clamp-force threshold alarm. The application's IO adapter assigns clampForceN and forceQuality before the program evaluates the alarm.

PROGRAM PRG_ClampAlarm
VAR
    clampForceN : REAL;
    forceQuality : TcForge.E_IO_Quality := TcForge.E_IO_Quality.UNKNOWN;
    alarm : TcForge.FB_AlarmThreshold;
END_VAR

alarm.cfg.common.bEnable := TRUE;
alarm.cfg.common.eSeverity := TcForge.E_AlarmSeverity.WARNING;
alarm.cfg.common.sMessage := 'Clamp force above 500 N';
alarm.cfg.common.tOnDelay := T#50MS;
alarm.cfg.fThreshold := 500.0;
alarm.cfg.bFailHigh := TRUE;
alarm.cfg.bFailLow := FALSE;
alarm(
    inpValue := clampForceN,
    inpValid := forceQuality = TcForge.E_IO_Quality.GOOD
);

Here the application deliberately requires GOOD quality. Choose how to treat CLAMPED according to the signal's meaning. HMI pages bind alarm.sts.active, .valid, .evaluationState, .eSeverity and .sMessage; acknowledgment uses OperatorAck(requestId) and its result query.

8.10 Anti-Patterns

  • Treating active = FALSE as proof of a healthy signal when valid = FALSE.
  • Disabling the alarm on IO loss instead of setting inpValid := FALSE.
  • Writing configuration or status through OPC UA; configuration belongs to the application and status to the alarm.
  • Calling an instance from multiple tasks or multiple times per scan. There is no automatic duplicate-call suppression.
  • Reassigning the rate detector to a new signal without invalidating its history.
  • Treating mailbox admission or Ack as proof that the machine condition cleared.

8.11 Checklist for a New Alarm FB

  1. Define a configuration with nested common : ST_Alarm_Cfg and its own criteria.
  2. Extend FB_AlarmBase, declare the configuration, signal inputs and inpValid := TRUE. The base already implements I_Alarm.
  3. Classify numeric operands before comparisons, conversions or arithmetic. Validate criterion-specific configuration.
  4. Compute the condition only for valid evidence and call _Evaluate exactly once per cyclic body. Pass resetTiming when changed criteria invalidate pending debounce credit.
  5. Keep state changes in the owning task, expose configuration/status read-only, and use the inherited queued operator acknowledgment API.
  6. Test invalidity, recovery, configuration changes, acknowledgment, timing and numeric extremes; update this page.