1 Programming standards

Read the architecture and qualification procedure before changing a control contract.

Names and modules

Use FB_ for function blocks, F_ for functions, ST_ for structures, E_ for enums and I_ for interfaces. Group a device with its configuration, status, state/fault types and tests. Configuration uses cfg, status uses sts (the machine uses Status). Status embeds the common device header. Keep module responsibilities focused.

Public commands return E_RpcMethodResponse. Prefer named arguments at call sites. Commands track requester identity; command rejection is not a device fault. Only fixed-identity Operator wrappers carry TcRpcEnable. Internal state and input signals are hidden from OPC UA; published status is read-only.

Execution and recovery

One task owns each FB. Run each cyclic body once per application scan. Sample inputs and map conditions first, then issue commands, update devices and apply outputs. The state machine makes one state transition per scan. Abort outranks Stop; output ForceSafe outranks ordinary output commands in the same scan.

Use IsFaulted() as the authoritative internal fault gate. Diagnostic snapshots refresh at the cyclic publication boundary. Reset follows the concrete recovery contract, not an unconditional permission to restart. Stop/Abort/ForceSafe have explicit state/priority rules and bypass the ordinary source/fault gate.

Detect faults before applying final outputs. Device methods record intent; physical completion comes from feedback. Normal step work stops on faults, while shutdown steps must remain executable. Positive travel timeouts and output pulse durations are required. Validate configurable ranges on every cyclic evaluation so a live edit cannot bypass validation.

Conditions

A permissive is a non-latching operational condition. An interlock latches a failure until fresh good input and Reset. Declare nRequired independently of mapping calls; missing required conditions inhibit operation. nBypassable declares which present conditions the application may bypass. Missing required conditions cannot be bypassed. Never treat these standard PLC blocks as safety-rated logic.

Stopping/fallback must not depend on ordinary motion permission. Do not reorder input mapping to trick a fault gate into accepting a command; use Stop, Abort or ForceSafe and the device's explicit recovery contract.

IO, persistence and diagnostics

Hardware AT allocations live only in the application. Library blocks receive ordinary input values and return output values. Input quality must be supplied by the adapter and included in required device conditions where appropriate.

Keep retained configuration/history separate from volatile operating state. Restoration of saved output intent is explicit and disabled by default. Reset and ForceSafe clear saved output intent. Validate persistent storage on the actual runtime; declarations alone do not guarantee survival of power loss.

Raise faults with a stable code, short source and actionable reason. Repeated current codes do not create repeated ring entries. History is bounded to eight entries. Keep cyclic string work bounded and measure task load on representative hardware before deployment.

Source files and tests

TwinCAT XML must be UTF-8 without BOM. Methods are POU children; Folder elements are siblings referenced by FolderPath. Preserve CDATA for declarations and ST. Exit is a reserved keyword; use Exiting for the lifecycle signal.

Test public behavior instead of duplicating implementation. Stateful multi-scan tests retain their FB/timer instances in suite scope. Cover invalid quality, missing required mappings, conflicting commands, timeouts, reset/retry, startup and shutdown. Use test probes only for diagnostic or persistent-image injection that has no ordinary public API. XML checks are not a PLC compiler.