Regulatory control

TcForge includes calculation blocks for common bounded analog and time-proportioned control. They accept conditioned process values and quality from the owning cyclic task. They do not select command sources, write %I or %Q, persist an operator request, or expose RPC methods. The application owns those concerns and routes the calculated demand through its output device and interlocks.

The blocks are inspired by the control patterns in rw-twincat-core's Regulatory Control folder. Their implementation and interfaces follow TcForge's quality, single-owner, and safe-output contracts rather than the reference project's source-handler and persistence design.

Block Purpose Safe response
FB_HysteresisControl Two-threshold BOOL demand for heating, cooling, filling, or venting Demand OFF
FB_BangBang Maps hysteresis demand to two numeric CV values CV zero and demand OFF
FB_PID_Full Cyclic PID with output limits, ramps, manual/hold, and tracking Configured safeCv
FB_TempController PID plus 0–100% cyclic PWM and standby setpoint Duty zero and PWM OFF
FB_SwitchingPvPid Switches between two independently tuned PV/PID channels for one CV Shared safeCv for a bad selected PV; zero for an invalid shared contract

Integrating a loop

Call a block once per owning task cycle with enable, a finite PV, and pvQuality := E_IO_Quality.GOOD. Feed its result to an application-owned output device only when the block reports sts.ready; also apply the machine's permissives and interlocks there. The application is responsible for retaining or arbitrating operator setpoints and manual requests. A physical safety function, where required, must remain independent of these software calculations.

Hysteresis uses low < high. With onBelowLow := TRUE, demand turns ON at or below low and OFF at or above high; FALSE reverses that direction. Invalid quality, enable, thresholds, or PV clears the old demand. On recovery, a PV inside the deadband does not re-energize from remembered state. FB_BangBang exposes the same status and maps ON to highValue, OFF to lowValue.

PID contract

ST_PID_Full_Cfg supports two gain forms:

  • Ideal form (standardForm := FALSE): kp is CV/PV, ki is CV/(PV·s), and kd is CV·s/PV. The calculated terms are kp·error, integrated ki·error·dt, and derivative on PV.
  • Standard form (standardForm := TRUE): proportional gain kp, integral time integralTime, and derivative time derivativeTime; the effective integral gain is kp/Ti and derivative gain is kp·Td. Zero times disable their respective terms.

Setpoint and CV ramp rates are engineering units per second; zero disables a ramp. reverseActing changes the error sign. derivativeTau enables a first-order derivative filter. CV and integral limits are independent. Integration is limited to the reachable CV boundary rather than accumulating beyond it, and sts.saturated reports a requested CV beyond that limit. A configuration edit clears prior controller history for one safe scan.

manual requests a bounded manualCv and tracks the integral bias so automatic control can resume near that value. hold freezes the CV while retaining current history. track is a one-scan bounded CV handoff for a different controller. These are calculation modes, not authorization or source-priority mechanisms. Resolve competing requests before calling the block.

cycleTime := T#0MS reads the owning task period. An explicit cycleTime is useful in deterministic test fixtures. maxDt bounds that declared calculation period, resets history, and emits safeCv when exceeded. It does not measure elapsed wall time or detect skipped task cycles; the owning application should apply its execution-continuity policy to the output device. The block rejects nonfinite REAL input bits before doing floating-point comparisons or arithmetic.

PWM and PV switching

FB_TempController requires PID CV limits of exactly 0..100 percent and safeCv = 0, and a pwmPeriod from 100 ms to one hour. It advances a cyclic PWM phase using the configured or owning task period; duty is the PID CV. The optional standby request selects standbySetpoint. If the PID is not ready, duty and PWM go OFF in the same scan. Size the PWM period to the physical switching device and process; this block does not implement an independent overtemperature cutoff.

FB_SwitchingPvPid has one PID configuration per PV and demands identical CV limits and safe CV for both. The inactive PID is reset each scan. On source change, the newly selected PID tracks the previous valid CV for one scan; subsequent scans regulate using its own tuning. A bad selected PV fails to the shared safe CV and invalidates the prior selection, so recovery cannot reuse a stale handoff. The application decides which source is authoritative.

Generic closed-loop bench test

The Testing PLC contains FB_ControlLoopFixture, a bench-only PID composition with no %I or %Q mapping. The Python runner uses the existing FirstOrderAnalog plant and writes PV, quality, enable, and setpoint as a payload, then writes requestFrame last. The PLC's cyclic task copies the frame, computes CV, publishes status, and acknowledges appliedFrame. A 500 ms feed watchdog disables the PID and returns CV to zero when Python stops. Its watchdogTrips counter lets the runner distinguish an actual lost feed from slow ADS communication. A timed-out or uncertain ADS frame is never replayed by the Python transport.

After activating the Testing application on a dedicated runtime, run:

artifacts/sim-venv/Scripts/python.exe -m tcforge_sim.control_loop --target <AMS-Net-ID> --port 853 --output artifacts/control-loop-bench

The runner checks convergence, same-frame response to bad quality, recovery, feed loss, and explicit disable. It writes JSONL and JUnit evidence. This fixture tests the PLC calculation and ADS exchange against a generic physical response; it does not qualify a real sensor, fieldbus, actuator, or machine safety function.

The TcUnit suites FB_HysteresisControl_Test, FB_RegulatoryControl_Test, and FB_RegulatoryControl_Edge_Test cover thresholds, gain forms, derivative filtering, output limits, mode changes, quality loss and recovery, PWM/standby, and PV switching. The source build and bench evidence are tracked in PROGRESS.md.