Foundation qualification

TcForge is a foundation under development, not a qualified production release. Source checks can run without TwinCAT; compiler, runtime and machine acceptance evidence are required before release. Installation and qualification progress is tracked in PROGRESS.md.

Architecture decisions

Daily development uses TwinCAT/TcForge.sln, with the core library and all three consumers in one TwinCAT project. [TcForge] resolves directly to source; the TcForgeExample project owns the application blocks and simulation bridge. Testing and Simulation reference that source project. In isolated test/simulation profiles the example has no runtime instance or boot build. Beckhoff documents this workflow under referenced PLC libraries. Run scripts/build_development.ps1 for a source build and run_tcunit.ps1 -Development for source-based bench tests. Neither requires a TcForge library installation or a version bump. Development results are not installed-artifact release receipts. The artifact qualification scripts explicitly select installed core-library references before building/testing and restore source profiles after closing XAE. Do not run engineering scripts while manually editing the same files.

  • Keep the device base, composed alarms and modular library. Use the base fault state for command validation. Status.AtRecoveryStep describes odd steps; Status.Faulted mirrors IsFaulted() when the machine publishes status.
  • One PLC task owns each device and its command calls. A scan samples inputs, evaluates conditions, consumes commands, updates state, applies output policy, then publishes status. There is no supported shared-instance multi-task API.
  • The state machine consumes requests once. Abort outranks Stop; Stop outranks ordinary commands. A pending ordinary command cannot replace another pending request. Acceptance means admitted for the next scan, not physical completion.
  • Condition configuration and freshness are separate. nRequired is a configured requirement mask, independent of whether MapInput was called. Configure it before operation. Missing required conditions cannot be bypassed. Optional unmapped bits retain the good-by-default behavior for intentionally optional conditions.
  • Default output recovery is inhibited. Retained command restoration and holding a value during invalid quality each require explicit configuration. Neither setting bypasses a device fault or ForceSafe.
  • Device blocks expose ordinary signal inputs and outputs. Hardware allocation and terminal mapping live exclusively in the application. Simulation uses the same public contract and cannot switch a hidden hardware path inside a device.
  • Program methods are not RPC-enabled. Only Operator* wrappers are exposed, with operator identity fixed inside the PLC. Source locking is arbitration; authentication and method authorization belong in the OPC UA server setup. No instance may be called from an arbitrary second PLC task. Validate RPC execution in the owning PLC task during qualification.
  • These are ordinary process-control interlocks, not safety-rated PLC functions. Machine safety functions remain in the machine's appropriate safety system.

Output and recovery contracts

  • Output startup is inhibited. restoreCommandOnRestart is an explicit opt-in and also requires a valid saved-command marker. ForceSafe/Reset invalidate that marker; default FALSE/zero is not sufficient restoration evidence.
  • BAD/UNKNOWN quality disarms output. Default behavior applies safeOutput or safeRaw; holdOnBadQuality may hold only while quality remains invalid and no fault/ForceSafe overrides it. Recovery requires a fresh accepted command.
  • ForceSafe applies electrical/raw fallback on the next cyclic call, bypassing pulse/debounce/inversion, and outranks ordinary output commands for that scan.
  • SetOff is a logical command, so inversion still applies. It is not ForceSafe.
  • Actuator faults remove coils in the detecting scan. Abort/Reset inhibit hold coils until an explicit new motion command, including rearming at a known position.
  • State-machine Reset requires STOPPED and healthy running conditions. Retry handles designated step faults; Stop/Abort perform operational shutdown.

Outputs are process-image commands, not proof that a terminal or actuator changed physically. Use actual feedback for physical confirmation. Analog sts.rawReal is the applied raw command; when outputInhibited is true, sts.value must not be interpreted as valid engineering-unit output feedback. Invalid output types produce zero raw bits. A configured fallback must be appropriate for its terminal.

Persistent storage must be configured and tested for the chosen runtime. The library preserves diagnostic history separately from volatile operating state.

Verification available without installation

From the repository root:

python scripts/check_repository.py
python -m unittest discover -s scripts/tests -v

The source CI job checks XML, compile inputs, test registration, direct library pins, RPC boundaries and test-project isolation. It does not prove ST type correctness, virtual dispatch, timer behavior or persistent storage. Release validation requires exact source test identities; an unrelated report with the same count fails. Build provenance and transitive dependency verification remain separate qualification requirements.

Repeatable Windows build

With the sibling twincat-mcp helper built and TcUnit installed, run:

powershell.exe -NoProfile -File scripts/build_twincat.ps1

Use -McpRoot if the helper repository is elsewhere. This checks all library objects, exports/installs the current library from TwinCAT/TcForge.Library.sln, then builds the isolated tests, example and standalone simulator against it. Errors or warnings stop this workflow. Build results and the library are written to artifacts/, including TcForge-library-check-all.json. The script selects Release|TwinCAT RT (x64) and requires the exact XAE baseline from toolchain.json; requested and effective versions are recorded in each result. Missing versions and failed selection cannot silently choose another compiler. It does not activate or restart a runtime.

To qualify consumption of an exported artifact from a fresh library repository:

powershell.exe -NoProfile -File scripts/verify_clean_library_install.ps1 -Library artifacts/TcForge.library -Output artifacts/fresh-library-check

The output directory must be new. This copies consumer sources without compiler caches, installs the supplied artifact into a uniquely named repository, and checks actual resolved TcForge paths and hashes before and after each consumer build. Exact dependency resolutions, compiler version and zero warnings remain required. Cleanup removes only the temporary repository registration and verifies the original repository order and existing System TcForge files. The copied sources, installed artifact and evidence remain in the output directory. This qualifies fresh TcForge consumption on the existing engineering installation; it does not qualify a clean Windows installation.

The sibling helper must be rebuilt with the exact-version and owned-process launcher changes. It launches XAE in embedded automation mode with the installed native DLL paths, attaches only to that process's DTE, and closes only that owned process. Repository scripts also initialize their own native DLL path. Neither requires changing the machine PATH or Docker settings.

dependencies.lock.json records effective references and loaded library versions for all four build projects. The build compares fresh XAE resolution and library signature captures against this lock, including transitive dependencies. A wildcard requires one concrete matching loaded-library signature; an installed file alone is insufficient. Normal builds never update the lock. For deliberate dependency changes, capture with scripts/capture_dependency_resolutions.ps1, produce a candidate with scripts/dependency_lock.py, review it, and rebuild. When the library also needs rebuilding, build_twincat.ps1 -CaptureDependencies exports, installs and builds the consumers into a fresh artifacts/dependency-candidate-* directory. It captures dependencies without comparing the old lock and deliberately produces no qualification receipt. Review the candidate, update the lock, then run the normal strict build; capture mode is not a qualification pass.

Successful builds retain a bundle under artifacts/builds/<buildId>/, including the library, compiler results, dependency captures and build manifest. artifacts/build-evidence.json points to the latest bundle through its recorded canonical manifest path. Source, toolchain and helper identities are checked before and after engineering operations. Only toolchain notes and qualification are excluded from the compilation digest; qualification is checked separately. These local records detect stale or mixed artifacts; they are not signed attestations.

To rebuild and run tests on the dedicated Windows RT target:

powershell.exe -NoProfile -File scripts/run_tcunit.ps1 -Target <ams-net-id> -Platform 'TwinCAT RT (x64)'

This replaces the target configuration and restarts it. Evidence runs require the platform in toolchain.json; another platform needs a deliberate toolchain change and new build evidence. The runner rebuilds the selected platform in the same XAE session immediately before activation; cached symbols from another platform must not be reused. Build, simulation activation and test scripts share an exclusive XAE lock. Run all engineering operations sequentially, including manual/MCP operations that do not participate in that lock.

Use -CycleTimeMs 1 for the 1 ms qualification run (the default is 10 ms). The runner sets the PLC task, system task and cached PLC context before XAE loads the project, restores the source profile after closing, and verifies the actual running period in the JUnit exporter. Each run creates a new directory; -RunDirectory may choose its location but cannot overwrite existing evidence. The runner requires a current build manifest and verifies that the installed TcForge library matches its artifact. Override -BuildEvidence or -InstalledLibrary for explicit bundle/repository locations. JUnit and its receipt bind the exact tests, actual period, target, source and library to one fresh run. The receipt is finalized only after source profiles are restored, while the engineering lock is still held. Re-exporting old results cannot create a bound run.

TwinCAT qualification after installation

  1. toolchain.json records the installed 3.1.4026.26 engineering baseline, Usermode Runtime 1.26.2 and the TcUnit 1.3.0.0 dependency. Direct Beckhoff library versions are pinned from the installation. Verify effective resolutions in the compiler, including transitive dependencies, and rebuild all projects. Record any deliberate toolchain changes before qualifying another baseline.
  2. Build/check all library objects, including unused ones. Export/install the current checkout's TcForge 2.0.0.0 library before building Testing, TcForgeExample and the standalone simulator. Their references are exact, not a wildcard selecting an older installed library. Record commit, artifact SHA-256, dependency versions, compiler version and warnings. Do not suppress new compiler warnings globally.
  3. Open TwinCAT/TcForge.Tests.sln. It contains only the Testing application, no example application or IO devices, no fixed target and no CPU reservation. Explicitly select an isolated Usermode Runtime/test target. The task is checked in with autostart disabled; the test runner must enable it for the run. Do not run two projects against the same runtime simultaneously.
  4. Build, activate and run Testing (ADS port 853, task Testing) with scripts/run_tcunit.ps1, supplying the target and platform explicitly. Capture every test result; a timeout, skipped test, or missing suite is failure. Run again from a fresh PLC initialization to detect persistent test contamination.
  5. The runner exports individual results automatically. The exporter reads the pinned TcUnit 1.3 instance layout over ADS, checks test identities against source, rejects unfinished results and detects runtime reinitialization during capture. Retain the printed run directory, its tcunit.xml, evidence receipt and activation-build JSON. A manual export is useful for diagnostics but cannot replace the runner's fresh provenance token and completed receipt.
  6. Run powershell.exe -NoProfile -File scripts/verify_operator_rpc.ps1 -Target <test-ams-net-id> against the activated Testing fixture. The verifier only addresses MAIN.rpcOutput, MAIN.rpcUninitialized and the context probe. It verifies deferred output mutation, owner-task dispatch, cancellation, duplicate IDs and 16 concurrent ADS clients. Keep its output with the build evidence. Then exercise the same contracts through the actual OPC UA server: locked normal commands queue but their final result rejects; program calls still work; LockSource/SetBypass/core methods are not callable. Verify roles, credentials, certificates and the published symbol allowlist. Test conflicting cyclic ownership, server reconnects and runtime restarts. ADS RPC verification alone does not qualify the OPC UA server or its security configuration.
  7. Execute the restart matrix below. Run timing tests at 1 ms and 10 ms task cycles. Then test representative real hardware for bus loss, feedback loss, safe-state behavior and cycle-time budget. Usermode execution cannot qualify physical IO response time or real-time scheduling.
  8. Store signed/reviewed acceptance evidence with the release, mark qualification verified only when complete, and run python scripts/check_repository.py --release --build-evidence <bundle>/build-evidence.json --library <bundle>/TcForge.library --test-report <run-1ms>/tcunit.xml --test-report <run-10ms>/tcunit.xml. Both reports must bind to the same build. Source CI passing alone never qualifies a release.

Restart and persistence acceptance matrix

Execution-boundary and cyclic-ownership fixture

The standalone Simulation project includes two unmapped reference machines and an isolated digital output for architecture qualification. On a dedicated bench, first run scripts/activate_simulation.ps1 with the explicit target/platform, then run:

artifacts/sim-venv/Scripts/python.exe scripts/verify_architecture_boundaries.py --target <AMS-Net-ID> --output artifacts/architecture-boundaries

The output directory must be new. The runner verifies that the second program is cyclic, starts simulated movement, stops only PLC application 854 through ADS, writes Home/Start while execution is stopped, then resumes it. Both machines use recoverOnOnlineChange := FALSE; actual execution gaps must still inhibit motion. The PLC captures command responses and both coil bits on the first resumed scan. The runner checks held commands, explicit recovery and completion of a fresh cycle. This fixture has no IO watchdog and uses real system-task counters. It does not apply an online edit or measure electrical outputs while PLC execution is stopped.

The ownership case first executes an operator command in the owner task. It then queues a second command and yields the instance to a different cyclic task for one call. The owner resumes after that call, checks cancellation of the queued command and rejection of a new command, and verifies the latched ownership fault. The handoff serializes these deliberately invalid calls; passing does not make arbitrary concurrent FB calls or direct program methods safe. Each device still requires exactly one cyclic owner. See Beckhoff's PLC task linking interface.

JSON and JUnit record the observed results, and cleanup returns the application to RUN with the fixture outputs off. This ownership case is one-shot: reactivate a fresh fixture before repeating it. Restore the normal application separately after qualification.

Acceptance cases

Use an isolated test project with no physical IO. Call each block once per scan. For each case, record before/after command, applied output, fault and history. Capture the first resumed scan as well as settled status. Distinguish a PLC stop/start, a PLC reset, a TwinCAT system restart and an online change in the evidence; one operation does not qualify the others.

The reference/simulation composition uses FB_ExecutionContinuity with the owning system task's CycleCount and the PLC application's OnlineChangeCnt. Its interruption response cancels intent and requires explicit recovery; standalone devices have no implicit online-change contract. See the execution-continuity contract for counter sources and limits. In particular, it cannot act while PLC code is stopped or detect a stop/start that misses no system-task tick.

Case Expected result
Default output, command ON/nonzero, orderly runtime restart Inhibited; configured fallback; a new command is necessary
Same with explicit restore enabled and valid persisted image Saved command resumes only with saved-command validity, BootDataLoaded TRUE, OldBootData FALSE, acceptable quality and no active fault
Missing or backup image, even with a saved-command marker Old intent is invalidated; outputs remain inhibited until a fresh accepted command
Restore enabled but startup quality BAD/UNKNOWN Inhibited; quality recovery alone cannot resume
Restore enabled with no valid saved-command marker, including inverted DO/nonzero AO fallback Inhibited at configured fallback; default FALSE/zero cannot arm output
ForceSafe/Reset followed by restart Saved operating intent has been cleared; default fallback remains
Active actuator hold, then Abort/Reset/restart No automatic coil energization from feedback alone
Record fault, clear it, orderly restart History survives only when persistent storage is configured and saved correctly; active fault is reevaluated
Restored alarm latch with invalid startup input Active latch and recognized configured severity remain visible; invalid evidence cannot clear it
Restored acknowledged alarm latch No second Ack required; valid clear evidence is still required
Cold reset / reset origin / missing or incompatible persistent image Apply the documented reset-class storage semantics; default operating intent remains inhibited
Reference machine running, PLC stop/start that skips system-task cycles First resumed scan cancels intent and inhibits outputs; explicit Reset/Home and fresh Start required
Same with a stop shorter than the simulation watchdog Counter interruption must still invalidate session/epoch; do not rely on watchdog expiry
Implementation-only and declaration-changing online changes, idle and moving Default recovery policy cancels intent and invalidates epoch. Explicit compatible-implementation preservation requires no execution gap or owner fault; declaration/layout changes require recovery. Qualify each policy separately
Home/Start coincident with detected interruption Command is rejected/consumed, cannot execute later while held; explicit recovery and a fresh command edge required
Queued remote command then runtime restart Pending intent and results are cleared; unknown result must not trigger automatic replay
OPC UA server restart/reconnect with PLC still running PLC mailbox state remains authoritative; reconcile results/status without replaying uncertain intent
Real power interruption on the qualified IPC Verify the actual UPS/persistent-save mechanism; declarations alone do not prove durability

The source tests exercise fresh initialization and public lifecycle behavior; multi-scan watchdog/motion tests use real TON time. Restart-image injection tests are distinct from this matrix and cannot replace runtime/power-cycle evidence. The saved-command marker and restored-alarm publication policy are implemented; the full matrix remains open. On the dedicated 3.1.4026.17 bench, short/long PLC stop/start passes at 1 ms and 10 ms. Direct ADS RESET/RUN and orderly system restart pass the standalone fixture's saved-intent/configuration, alarm-latch and fault-history checks. ForceSafe/Reset invalidation survives both operations. Separate controlled missing/backup/malformed-image cases and actual online changes now have bench evidence in PROGRESS.md, including moving declaration recovery and compatible implementation preservation. Sudden power loss remains unqualified. Reset-origin passes separately: engineering logout and controller application removal are verified before same-source reload; persistent markers, intent, alarms and history then initialize. The separate XAE cold-reset path passes after confirming engineering login, waiting for reset STOP, and verifying subsequent RUN. See PROGRESS.md for retained evidence.

Use Beckhoff's remanent-variable semantics to define reset-class expectations, and its online-change operating cases to distinguish initialization and instance-copying behavior. Record the actual runtime version, image status and save mechanism with those results.

Release evidence

Retain the commit ID, library SHA-256, toolchain/dependency manifest, clean build and check-all-objects logs, complete test report, repeat-run results, restart/RPC matrix, hardware acceptance results, and operating contracts. Production adoption requires this evidence and machine-specific commissioning, even after every source change in this foundation revision is complete.