OPC UA qualification

OPC UA's TCP endpoint and its ADS backend are different addresses. The bench endpoint is opc.tcp://192.168.1.224:4840. Example uses ADS 851, Testing 853, and Simulation 854. Activating one solution does not start the other solutions. Browse success alone is insufficient: stale TMC symbols can remain visible while the backend reports Target port not found. Check device error, PLC RUN, and a nonzero cyclic owner before testing methods.

Server configuration

Use filtered TMC import (AutoCfg 4041), the actual runtime's ADS port and its [BootDir]/Plc/Port_<port>.tmc. Use a separate named device per runtime. Keep SignAndEncrypt enabled, use Basic256Sha256 or a supported stronger policy, and explicitly trust each client certificate. Disable AutomaticallyTrustAllClientCertificates. Pin the server certificate obtained through an independently authenticated channel. Client private keys stay on the client. Certificate replacement requires renewing the corresponding trust entry.

The bench explicitly trusts the development PC's UAExpert and qualification certificates. A replacement PC needs its own trusted certificate as well as a valid user account. Administrator uses OS authentication and the same credential as Windows/SSH. Store recovery credentials in the company password manager; the developer's local DPAPI copy is not a portable recovery backup.

Use OS-authenticated users and namespace/node permissions for deployed clients. Do not use Administrator for an ordinary HMI. A read-only user must not inherit the default Users group's PLC write rights. Read/browse access is 0x0000000B; grant method execution only on the intended Operator methods, using node-level AccessInfos. Configuration and raw output writes must remain inaccessible. The exact commissioned roles depend on the application; the bench's temporary read-only qualification account is removed after testing.

Repeatable runner

Install python -m pip install -e "./python[opcua]". The runner requires an existing ADS route and a trusted certificate/private key. Passwords come from environment variables, never command-line values or report files. For the current Windows bench, retrieve the local encrypted credential into the process environment:

$env:TCFORGE_OPCUA_PASSWORD = (Import-Clixml -LiteralPath "$env:LOCALAPPDATA/TcForge/bench/192.168.1.224-Administrator.credential.xml").GetNetworkCredential().Password
$certDir = "$env:LOCALAPPDATA/TcForge/bench/opcua"
try {
    artifacts/sim-venv/Scripts/python.exe scripts/verify_opcua.py `
      --endpoint opc.tcp://192.168.1.224:4840 --target 172.18.236.100.1.1 `
      --port 851 --fixture Example --namespace urn:BeckhoffAutomation:Ua:PLC1 `
      --certificate "$certDir/client.der" --key "$certDir/client.pem" `
      --server-certificate "$certDir/server.der" `
      --application-uri urn:tcforge:bench:qualification --user Administrator `
      --ads-dll-directory 'C:/Program Files (x86)/Beckhoff/TwinCAT/Common64' `
      --clients 16 --output artifacts/opcua-example-new-run
} finally {
    Remove-Item Env:TCFORGE_OPCUA_PASSWORD
}

Each output directory must be new. JSON and JUnit include setup/cleanup failure, runner/certificate hashes, individual outcomes and explicit scope. A successful run does not set production qualification metadata. Example mode requires its outputs inhibited and checks sampled output state, not electrical pulse timing.

To restore the Example on a dedicated bench:

powershell.exe -NoProfile -File scripts/activate_example.ps1 `
  -Target 172.18.236.100.1.1 -Platform 'TwinCAT RT (x64)'

This replaces the active target configuration. It enables task and boot autostart, rejects warnings, preserves engineering profiles, and checks that the actual cyclic counter advances. Keep UAExpert pointed at the Example device on 851; allow the OPC UA server to finish reloading symbols after activation.

Testing mode requires the Testing solution active on 853 and an OPC UA device pointing at its filtered TMC. Set --fixture Testing --port 853 and its namespace. It controls only MAIN.enableRpcPump and the MAIN.rpcOutput source lock through ADS. This lets the suite prove deferred execution, one pending command under independent-client load, priority cancellation, source-lock enforcement and the safe-command exception. Cleanup restores the lock, resumes the pump, and checks ForceSafe completion/output off. Never map this fixture to physical outputs.

Optional --observer-user and TCFORGE_OPCUA_OBSERVER_PASSWORD exercise read access and method denial for an already provisioned account. Omission is recorded and does not imply role qualification. The runner does not change users, trust, firewalls, or server configuration. Untrusted-certificate rejection, certificate renewal and the complete commissioned permission matrix remain separate checks.

Restart troubleshooting

Check the layers independently: TwinCAT RUN/cyclic execution over ADS, an OPC UA TCP listener, then an authenticated session and PLC device status. An XAE restart receipt alone does not verify OPC UA readiness. On the dedicated bench, a fresh XAE-managed restart needed additional server startup time before authenticated access recovered. Launching the server executable manually was not a verified replacement for its TwinCAT-managed COM startup. Beckhoff describes this registration and startup relationship.

A separate Secure ADS reconnect failure after reboot was recovered using Beckhoff's Add-AdsRoute with -SelfSigned, the existing expected peer -FingerPrint, credentials loaded privately, and -Force. Certificate validation was retained. This recovery does not establish the cause or prove unattended reconnect durability; that remains an open bench issue in the progress tracker.

Acceptance still required

Keep the Q4 restart/online-change, Q5 conflicting-task/application role matrix, and Q6 physical IO/task-load gates in the progress tracker. A software restart does not stand in for abrupt power loss. Local source hashes and unsigned reports do not stand in for validation on a fresh engineering environment.

References: Beckhoff security configuration, PLC symbol configuration.