7 Sequencing

FB_StateMachine owns machine state, current/next step, a step timer and device faults. FB_Step owns each step's Entry, Execute and Exiting lifecycle. Use even steps for work; the following odd step is a recovery location. State ranges are: HOMING 1000–1999, STOPPING 2000–2999, RUNNING 3000–3999, PAUSING 4000–4999, ABORTING 5000–5999 and PROCEEDING 6000–6999.

Commands

Command Valid state and result
Home STOPPED → HOMING, when home/auto permissions and running interlocks are good
Start READY → RUNNING with start/auto permissions and no fault
Pause RUNNING → PAUSING; completion enters PAUSED
Proceed PAUSED → PROCEEDING; completion re-enters the paused step
Stop READY → STOPPED; other operational states → STOPPING; does not downgrade ABORTING
Abort Any operational state → ABORTING; cancels queued Home even before movement starts
Reset STOPPED only, no active submodule fault and good running interlocks; failed Abort also requires inpShutdownConfirmed
Retry Recorded ordinary-step failure at its odd recovery step, including application fault codes; validates source/interlocks and re-enters the previous even step

Reset accepts either valid requester regardless of source lock; an invalid requester is rejected before recovery state changes.

Commands are consumed once; Abort outranks Stop and ordinary commands. A scan makes at most one machine-state transition. Running interlocks and submodule faults request Abort. Shutdown steps still execute while the triggering fault remains; completion enters STOPPED without hiding the fault. Ordinary steps stop executing on a fault. Status.AtRecoveryStep is separate from Status.Faulted.

Auto-run is an explicit cfgAutoRun opt-in. A completed RUNNING cycle may restart from READY only with good permissions/interlocks and no fault. The example defaults to manual operation. Rejected Start commands do not become latent start requests.

Conditions and call order

Use cfgHome, cfgStart, cfgProceed, cfgAuto, cfgRunning to configure required and bypassable masks before operation. Feed values using MapHomeCondition, MapStartCondition, MapProceedCondition, MapAutoCondition and MapRunningIntlk before the state-machine cyclic call. Missing required interlocks latch; restore fresh inputs, ResetRunningIntlk, then Reset the stopped machine.

Call the state machine before the steps. Call every FB_Step instance once each scan, including inactive ones. The following state-machine call checks that the active even step was called exactly once. A missing implementation or duplicate call raises a distinct configuration fault. Detection occurs on the next state-machine call; it does not undo application actions already issued that scan. Entry fires once, Execute maps completion conditions, Exiting runs cleanup once, and Advance sets the next step. nNextStep := 0 completes the sequence. Mappings made during Execute are evaluated on the next step call. Configure nRequired independently so a missing MapPerm call cannot silently satisfy a required completion condition.

step(sm := sm, nStep := 3000, nNextStep := 3002,
     nRequired := ULINT#3, nTimeout := 10, sName := 'Wait for device');
IF step.Execute THEN
    step.MapPerm(nIndex := 0, sDescription := 'In position', bValue := inPosition);
    step.MapPerm(nIndex := 1, sDescription := 'Quality good', bValue := qualityGood);
END_IF;

Step boundaries and failed shutdown

A destination must be zero (complete the state) or a different even step in the current state's range. Negative, odd, cross-state and self destinations fault before lifecycle outputs execute. Loops use two or more work steps. A valid number with no corresponding called instance faults when selected. Keep each instance's nStep identity fixed; configure destinations dynamically when branching.

nTimeout = 0 disables timing. Valid positive values are 1–356400 seconds (99 hours), matching the step timer range; values outside that range are invalid. Positive timeouts cover the entire active lifecycle, including Entry and Exiting, and expire at elapsed >= timeout. A failure suppresses that step's lifecycle outputs immediately. Nonpositive application fault codes normalize to StepUserFault. Application code must also gate its final physical outputs on current fault and quality conditions; clearing lifecycle flags cannot revoke commands already issued.

Failure location Result on the next state-machine call Recovery
Homing, Running, Pausing, Proceeding Following odd recovery step; normal work inhibited Explicit Retry with healthy interlocks/submodules, or Stop/Abort
Stopping Aborting, first step 5000; original fault retained Execute the application's Abort sequence
Aborting Stopped with latched ShutdownFailed; work inhibited Application confirms physical shutdown through inpShutdownConfirmed, then explicit Reset

Status.FailedStep identifies the failed step until Reset. The fault history retains individual failure diagnostics, including escalation. STOPPED alone does not prove physical shutdown. inpShutdownConfirmed defaults false and must be derived from appropriate application feedback, not merely the state enum or output command. Normal successful Stop/Abort completion retains the initiating fault until Reset. A failed shutdown is not retried through an odd step.

Stop/Abort sequences must implement actual output shutdown and confirmation in a machine application. The example is not a commissioned machine safety sequence.

A state transition publishes the new state and its first step in the same cyclic call. Abort from RUNNING therefore publishes ABORTING with step 5000 immediately; a pending running-step advance cannot delay or replace the abort entry step.